FIREX EC 43 Survival fire test: 240 minutes, circuit alive
Watch a cable coated with 1.6 mm of FIREX EC 43 Survival keep its circuit alive for 240 minutes + 15 minutes cooling at 750°C to IEC 60331-21, while standard XLPE failed at 6 minutes.
Test details
| Standard | IEC 60331-21 |
|---|---|
| Fire exposure | 240 minutes + 15 minutes cooling at 750°C |
| Test cable | XLPE 4-core 70 sq mm |
| Coating | FIREX EC 43 Survival, 1.6 mm dry-film thickness |
| Result | Circuit alive at 240 minutes. In the same test, standard XLPE failed at 6 minutes and FR-LS XLPE at 7 minutes. |