FIREX EC 43 Survival fire test: 240 minutes, circuit alive

Watch a cable coated with 1.6 mm of FIREX EC 43 Survival keep its circuit alive for 240 minutes + 15 minutes cooling at 750°C to IEC 60331-21, while standard XLPE failed at 6 minutes.

Test details

StandardIEC 60331-21
Fire exposure240 minutes + 15 minutes cooling at 750°C
Test cableXLPE 4-core 70 sq mm
CoatingFIREX EC 43 Survival, 1.6 mm dry-film thickness
ResultCircuit alive at 240 minutes. In the same test, standard XLPE failed at 6 minutes and FR-LS XLPE at 7 minutes.